20 corrections on record · 6 safety-relevant · newest first

Every NEC value in OhmBase is transcribed from the printed book and checked against it before it ships. When an error is found anyway, it is fixed in the source tables, pinned by a regression test so it cannot come back, and logged here with what was wrong, what changed and which results to re-check. Users are told inside the app (Profile → About) — nothing is patched quietly.

Calculator results show their sources: every figure carries the table or section it came from, and tapping it opens that entry in the app.

Grounding, tap, OCPD-location and motor-disconnect entries corrected from the 2026 book

2026-11-18 · fixed in v4.15.2 · NEC reference · Reference text only

A second read of the 2026 book, section by section, found reference text that was wrong. None of it fed a calculator. Two rules were stated wrong: parallel service raceways do not each need their own supply-side bonding jumper, because one jumper sized on the combined circular mils is allowed (250.102(C)(2)); and the motor disconnect may be left out only when the controller disconnect is lockable per 110.25 and either a disconnect at the motor is impracticable or adds hazards, or it is an industrial site with written procedures and qualified people (430.102 exception). Also fixed: the 230.40 exceptions described the wrong cases and missed the common-area exception; the transformer tap is 240.21(B)(3), not 240.21(C); OCPDs are now kept out of all bathrooms, showering facilities and locker rooms with showers (240.24(E)); and section numbers moved in 2026 (neutral sizing 250.24(D), motor branch-circuit protection 430.52(C)(1)(a) and (b)).

Verified against: NEC 2026, read in the NFPA free-access edition 2026-11-18.
Affected versions: Reference screens and one exam explanation only, v4.15.1 and earlier.

Reference entries corrected while moving the app to NEC 2026

2026-11-16 · fixed in v4.14.0 · NEC reference · Reference text only

Reading the 2026 book for the edition change turned up reference text that was wrong or out of date. None of it fed a calculator. Fixed: service-drop clearance above roofs is 8 ft 6 in, not 8 ft, and the 15 ft and 24-1/2 ft rows were missing (230.24); the burial-depth table had mislabeled rows and columns and no airport row (Table 300.7(A), was 300.5(A)); GFCI in dwellings has no 50 A limit, and the table now lists other occupancies, crawl-space lighting, appliances and outdoor outlets (210.8); AFCI covers all hotel and motel guest rooms, not only ones with cooking (210.12(D)); island and peninsula receptacles are no longer required (210.52(C)(2)); non-dwelling unit loads were old values (offices 1.3 VA per sq ft, not 3.5; hospitals 1.6, not 2); the working-space entrance rule (110.26(C)(2)); Table 8 has no weight column. Article 300 and Article 120 section numbers are updated to the 2026 book (300.3 → 300.5, 300.4 → 300.6, 300.5 → 300.7; dwelling demand factors are Table 120.45 and noncoincident loads 120.6).

Verified against: NEC 2026 (and NEC 2023 where noted), read in the NFPA free-access editions 2026-11-16.
Affected versions: Reference screens only, v4.13.3 and earlier.

Three 90 °C ampacities in Table 310.16 were wrong

2026-11-16 · fixed in v4.13.4 · Wire ampacity (Table 310.16) · Safety-relevant

Three cells in the 90 °C columns did not match the book. Aluminum 6 AWG read 60 A; the table gives 55 A, so 90 °C aluminum derated from that cell came out 5 A high. Copper 3 AWG read 110 A (book 115 A) and aluminum 300 kcmil read 255 A (book 260 A); both of those were low, not unsafe. The 90 °C column is the starting point when derating 90 °C wire, so the aluminum error could carry into a derated result.

Verified against: NEC 2023 and NEC 2026 Table 310.16, read in the NFPA free-access editions 2026-11-16 — the values are the same in both.
Affected versions: v4.13.3 and earlier: Wire ampacity tool and the Table 310.16 reference, 90 °C insulation.

Re-check any 6 AWG aluminum, 90 °C conductor that was derated for bundling or ambient temperature.

Box fill counted any number of grounds as one allowance

2026-11-16 · fixed in v4.13.4 · Box fill (314.16) · Sizing result changed

Up to four equipment grounding conductors share one volume allowance, but each one past four adds a quarter allowance. The calculator always used one allowance, so a box with five or more grounds could come out slightly too small: six 12 AWG grounds need 2.25 + 2 × 0.5625 = 3.38 in³, not 2.25 in³.

Verified against: NEC 2023 and NEC 2026 314.16(B)(5), read in the NFPA free-access editions 2026-11-16.
Affected versions: v4.13.3 and earlier, box fill with more than four equipment grounds.

Re-check boxes sized with five or more grounds that came out close to full.

Ambient correction above 140 °F used the lower factor of each pair of rows

2026-11-16 · fixed in v4.13.4 · Wire ampacity (ambient correction) · Sizing result changed

Table 310.15(B)(1)(1) has separate rows for 141–149, 150–158, 159–167, 168–176 and 177–185 °F. The app had merged them into two bands and used the lower factor for both (for example 0.58 instead of 0.65 for 90 °C at 141–149 °F), and stopped at 176 °F. Results were conservative. All five rows are now in the table and the select.

Verified against: NEC 2023 and NEC 2026 Table 310.15(B)(1)(1), read in the NFPA free-access editions 2026-11-16.
Affected versions: v4.10.0 – v4.13.3, ambient temperatures above 140 °F.

The standard ratings list started at 15 A instead of 10 A

2026-11-16 · fixed in v4.13.4 · Breaker sizing (240.6(A)) · Reference text only

Table 240.6(A) lists 10 A as a standard rating. The Breaker sizing tool and the reference table started at 15 A, so a load of 10 A or less was rounded up to 15 A.

Verified against: NEC 2023 and NEC 2026 Table 240.6(A), read in the NFPA free-access editions 2026-11-16.
Affected versions: v4.12.0 – v4.13.3, Breaker sizing.

Interlocked heat pump dropped the supplemental heat instead of the compressor

2026-11-16 · fixed in v4.13.3 · Load calc (optional method, heat pump) · Safety-relevant

For a heat pump with supplemental electric heat, the optional method carries the compressor at 100% plus 65% of the supplemental heat. When an interlock keeps the two from running together, the book says the compressor does not need to be added to the supplemental heat. With the interlock box checked the calculator did the reverse: it kept the compressor and dropped the heat. A 3.5 kW compressor with 10 kW of strip heat was carried at 3.5 kW instead of 6.5 kW, so the service could come out too small. Interlocked now carries the larger of the compressor (as A/C) or 65% of the supplemental heat.

Verified against: NEC 2026 120.82(C)(3) and NEC 2023 220.82(C)(3), read in the NFPA free-access edition 2026-11-16 — the wording is the same in both.
Affected versions: v4.7.0 – v4.13.2, optional method, "Heat pump + supplemental electric heat" with the interlock box checked.

Re-run any optional-method load calc that used the interlock box; the service size may step up.

NEC 2023 optional method took electric heat at 100% for every system type

2026-11-16 · fixed in v4.13.3 · Load calc (NEC 2023 optional method) · Sizing result changed

The heating-system factors of 220.82(C) — central electric heat 65%, four or more separately controlled units 40%, heat pump compressor plus 65% of supplemental heat — were not yet verified for 2023, so the 2023 optional method carried heat at 100% as a conservative placeholder (the 2026 path already applied them). The 2023 book has the same six items and percentages as the 2026 120.82(C), so both editions now use them. Results were on the high side, never undersized.

Verified against: NEC 2023 220.82(C), read in the NFPA free-access edition 2026-11-16.
Affected versions: v4.4.5 – v4.13.2 with the 2023 edition, optional method and electric heat entered.

No safety impact; re-run only if the earlier result pushed a service up a size.

Range Note 1 adder rounded every fraction of a kilowatt up

2026-11-08 · fixed in v4.13.0 · Load calc (ranges over 12 kW) · Sizing result changed

Table 220.55 Note 1 increases the Column C demand 5% for each kilowatt "or major fraction thereof" over 12 kW — 0.5 kW and up rounds to the next kilowatt, below 0.5 is dropped. The calculator rounded every fraction up, so a 12.1 kW range already received a 5% adder and a 14.4 kW range received 15% instead of 10%. Results were on the conservative side (never undersized).

Verified against: Web-verified 2026-11-08: Note 1 wording reproduced verbatim (IEEE-hosted NEC excerpt); rounding convention from open-exam-prep worked examples, Keentel and EC Magazine. Read in the 2023 and 2026 books 2026-11-16 (NFPA free-access edition): Note 1 wording matches.
Affected versions: All versions through v4.12.1 with a range rated between x.0 and x.5 kW over 12 kW.

No safety impact; re-run only if the earlier result pushed a service up a size.

Fixed electric space heat was taken at 65% in the 2023 standard method

2026-11-08 · fixed in v4.13.0 · Load calc (NEC 2023 standard method) · Safety-relevant

With the NEC 2023 edition selected, the standard (Article 220) calculation carried central electric heat at 65% of connected load. 220.51 requires 100% of the total connected load in the standard method (the 65% figure belongs to the optional method, 220.82(C)). Services with electric heat were UNDERSTATED. The 2026 path was already at 100%.

Verified against: Web-verified 2026-11-08: 220.51 text reproduced verbatim (IEEE-hosted NEC excerpt) and 2023/2026 summaries agree (sparkyblog, open-exam-prep, Keentel). Read in the 2023 book 2026-11-16 (NFPA free-access edition): 220.51 says 100 percent of the total connected load.
Affected versions: v4.7.0 – v4.12.1 with the 2023 edition selected and electric heat entered (earlier versions had the same 65% factor).

Re-run any 2023 standard-method load calc that included electric heat; the service size may step up.

Ambient-temperature correction used the 75 °C column for every insulation rating

2026-10-13 · fixed in v4.10.0 · Wire ampacity · Safety-relevant

The ambient-temperature select carried one set of factors — the 75 °C column of Table 310.15(B)(1)(1) — whatever insulation rating was chosen. 60 °C conductors were overstated (Cu 8 AWG at 114–122 °F read 30 A; the table gives 40 × 0.58 = 23.2 A) and 90 °C conductors understated. The factor is now read from the column matching the insulation, from the same table the reference screen shows.

Verified against: NEC 2023, Table 310.15(B)(1)(1)
Affected versions: v4.9.9 and earlier

Re-check any 60 °C (TW/UF) conductor sized with ambient correction in an earlier version — it may be undersized.

Overcurrent device sized from the 90 °C column with no termination limit

2026-10-13 · fixed in v4.10.0 · Wire ampacity · Safety-relevant

With 90 °C insulation selected the tool sized the breaker from the 90 °C ampacity and never applied 110.14(C): Cu 6 AWG with no derating read 75 A and an 80 A device, where the 75 °C termination column gives 65 A and a 70 A device. A termination-rating select (75 °C default, 60 °C, 90 °C listed) now caps the result at the termination column.

Verified against: NEC 2023, 110.14(C) and Table 310.16
Affected versions: v4.9.9 and earlier

Re-check any circuit sized with 90 °C conductors in an earlier version — the breaker may be one size too large for the terminations.

Jam ratio used bare-conductor diameters, missing real jam cases

2026-10-13 · fixed in v4.10.0 · Wire pulling · Sizing result changed

The jam-ratio check divided the conduit inside diameter by the bare conductor diameter instead of the insulated THHN/THWN-2 diameter. Three 8 AWG in ½" EMT read 3.53 ("no jam risk") when the insulated figure is 2.88, inside the 2.8–3.2 zone; three 1 AWG in 1¼" EMT read 4.12 instead of 3.09. The insulated diameter is now derived from the Chapter 9 Table 5 areas already in the app.

Verified against: NEC 2023, Chapter 9 Table 5 (areas) and Table 4 (internal diameters); jam zone 2.8–3.2 is an industry rule
Affected versions: v4.9.9 and earlier

Re-check three-conductor pulls planned with an earlier version — some "no jam risk" verdicts were wrong.

EV charging load rule corrected (220.57)

2026-09-10 · fixed in v4.5.9 · NEC reference · Reference text only

The electric-vehicle supply equipment entry described the load as nameplate only. NEC 220.57 requires the larger of 7,200 VA or the nameplate rating. Reference text only — no calculator used it.

Verified against: NEC 2023, 220.57
Affected versions: v4.5.8 and earlier (reference text)

Surge-protective device article corrected 280 → 242

2026-09-10 · fixed in v4.5.9 · NEC reference · Reference text only

The SPD entry cited Article 280, which was renumbered to Article 242 in the 2020 NEC. Reference text only — no calculator used it.

Verified against: NEC 2023, Article 242
Affected versions: v4.5.8 and earlier (reference text)

Motor minimum wire size was oversized by 2–4 sizes

2026-07-16 · fixed in v4.3.6 · Motor wiring · Sizing result changed

The motor tool picked the conductor from a separate hard-coded amps-to-AWG list that did not match Table 310.16 — 50 A returned 3 AWG where the 75 °C copper column puts 8 AWG at 50 A. The tool now reads Table 310.16 directly, with no parallel list to drift. Results were larger than required, never smaller.

Verified against: NEC 2023, Table 310.16 (75 °C copper)
Affected versions: v4.3.5 and earlier

Motor circuits sized with an earlier version are safe but may have been priced with more copper than the Code requires.

Rigid conduit (RMC) internal diameters were EMT values

2026-07-15 · fixed in v4.3.4 · Wire pulling · Sizing result changed

The jam-ratio check in the wire-pulling tool used EMT internal diameters for rigid conduit. Corrected to Chapter 9 Table 4 (½" 0.632 in through 3" 3.090 in). EMT values were already correct.

Verified against: NEC 2023, Chapter 9 Table 4
Affected versions: v4.3.3 and earlier

Re-check jam-ratio results for three-conductor pulls in rigid conduit made with an earlier version.

THHN/THWN-2 conductor areas corrected for 3 AWG, 2 AWG and 400 kcmil

2026-07-15 · fixed in v4.3.3 · Raceway sizing · Sizing result changed

Three Chapter 9 Table 5 areas mixed insulation families. Corrected: 3 AWG → 0.0973 sq in, 2 AWG → 0.1158 sq in, 400 kcmil → 0.5863 sq in. All other sizes were already correct.

Verified against: NEC 2023, Chapter 9 Table 5
Affected versions: v4.3.2 and earlier

Re-check conduit fills that include 3 AWG, 2 AWG or 400 kcmil made with an earlier version.

IMC, rigid and PVC raceway fill areas were wrong

2026-07-15 · fixed in v4.3.2 · Raceway sizing · Sizing result changed

IMC held a copy of the PVC column and rigid (RMC) was undersized; EMT was already correct. Every raceway area was re-transcribed from Chapter 9 Table 4 and triple-checked (π/4 × ID² = the printed 100% area = the printed 40% area ÷ 0.4).

Verified against: NEC 2023, Chapter 9 Table 4
Affected versions: v4.3.1 and earlier

Re-check IMC, rigid and PVC conduit fills made with an earlier version.

Single-phase motor full-load current was understated

2026-07-15 · fixed in v4.3.0–v4.3.1 · Motor wiring · Safety-relevant

115 V and 230 V single-phase full-load currents did not match Table 430.248 — a ½ HP 115 V motor read 4.4 A instead of 9.8 A, so the wire, breaker, overload and disconnect figures built on it were all too small. The 1/6, 1/4 and 1/3 HP rows were added at the same time. Three-phase motor data (Table 430.250) was not affected.

Verified against: NEC 2023, Table 430.248
Affected versions: v4.2.5 and earlier

Re-check any single-phase motor circuit sized with v4.2.5 or earlier — conductors and overcurrent protection may be undersized.

Found something that does not match your book? Email support@ohmbase.app with the table and edition. Verified reports go on this page.